TUNNEL LIGHTING

Temporary Tunnel Lighting – Lux Levels & Design Guide

Technical guidance on illuminance levels for temporary tunnel construction lighting, covering normal working lighting, workface considerations, long-run LED strip and emergency provision. Based on BS 6164:2019 for tunnel-specific design values and BS EN 1838:2024 / BS 5266-1:2025 for emergency lighting criteria.

01

Introduction

Tunnelling is wholly dependent on artificial light, so the lighting system and its power supply must be made as secure and reliable as the environment demands. The principal UK code of practice for health and safety in tunnelling is BS 6164:2019 — Health and safety in tunnelling in the construction industry — Code of practice. Its Clause 17, “Quality of illumination,” provides tunnel-specific recognised design guidance including mean lighting levels for the distinct areas within a tunnel.

UK legislation — the Workplace (Health, Safety and Welfare) Regulations 1992 and the Construction (Design and Management) Regulations 2015 — requires that workplace lighting be “suitable and sufficient.” BS 6164:2019 provides the recognised tunnel-specific design criteria that demonstrate compliance with that legal duty. Compliance with a British Standard is not itself a statutory requirement; the legal duty is to provide suitable and sufficient lighting, and the standard provides the recognised technical method for meeting it in tunnelling work.

General construction-site lighting guidance is also available in BS EN 12464-2:2024, but the tunnel-specific values in this guide come from BS 6164:2019, which is the dedicated code of practice for tunnelling.

02

How much light does a tunnel need?

BS 6164:2019 treats a tunnel as a set of distinct areas, each with its own mean lighting level. Walkways and tracks require a lower level for safe movement; general working areas and the tunnel face require a higher level for safe work. A single lighting arrangement rarely satisfies all areas simultaneously — the design should address each zone individually.

The values below are tunnel lighting design guidance from BS 6164:2019, not statutory legal minimums. They are the recognised design criteria for meeting the legal duty to provide suitable and sufficient lighting in tunnelling work.

03

Tunnel lighting design values

The table below sets out the tunnel-specific mean lighting levels from BS 6164:2019, Table 9.

TUNNEL APPLICATION
MEAN LIGHTING LEVEL
REFERENCE PLANE / ARRANGEMENT
Walkways and tracks
30 lx
At walkway level
General working areas
100 lx
At working surfaces
Tunnel face, excavation areas, areas with lifting operations
100 lx
At the working surface, illuminated from at least two suitably separated sources to reduce problematic shadowing

SOURCE: BS 6164:2019, CLAUSE 17.2, TABLE 9 — MEAN LIGHTING LEVELS

These are recognised tunnel-specific design guidance values, not statutory legal minimums. UK legislation requires lighting to be suitable and sufficient; BS 6164 provides the recognised tunnel-specific design criteria for meeting that duty.

04

Workface and task lighting

Achieving an average lux level alone is not sufficient at an active tunnel face. The lighting arrangement must also account for the dynamic and confined nature of the working face, where plant, personnel and moving machinery all interact in a restricted space.

BS 6164:2019 specifically calls for the tunnel face, excavation areas and lifting-operation areas to be illuminated from at least two suitably separated sources to reduce problematic shadowing. Beyond that, the workface lighting arrangement should consider:

  • shadowing cast by plant, personnel and the tunnel structure itself
  • glare from luminaires in a confined space, particularly for operators of moving machinery
  • lighting direction — light from behind or above the work can create shadows that obscure the task
  • moving machinery and the visibility of personnel in its vicinity
  • visibility of hazards at the face and along the spoil-loading path
  • uniformity across the working area, so that bright spots and dark patches do not create trip or strike hazards
  • supplementary machine-mounted or portable task lighting where the general tunnel lighting cannot reach the active face

General continuous tunnel lighting — such as a longitudinal LED strip run — provides the background illumination for safe movement and general work along the tunnel. It does not necessarily replace local task or machine-mounted lighting at the active working face, where the conditions above demand a dedicated arrangement.

05

Access and circulation lighting

Tunnel walkways and tracks require a mean lighting level of 30 lux at walkway level per BS 6164:2019. This is the level that allows safe movement of personnel along the tunnel, including to and from the working face. Because a tunnel is a long, narrow space, the continuity of illumination along the access route is as important as the average level — dark zones between widely spaced point luminaires create trip and orientation hazards.

Continuous LED strip is particularly well suited to tunnel circulation lighting. Run longitudinally along the tunnel, it provides continuous illumination along the full length of the access route rather than the pools of light produced by spaced point luminaires. The engineering and practical benefits include:

  • continuous longitudinal illumination along the access route, improving visual continuity for personnel moving through the tunnel
  • reduced dark zones between luminaires compared with spaced point sources
  • long-run installation from a single or limited number of power feed points, reducing the need for intermediate distribution
  • suitability for temporary infrastructure installations where the lighting is deployed and recovered as the tunnel advances

These are engineering and product benefits of continuous LED strip for tunnel circulation. The actual illuminance achieved depends on the product, output, mounting height, spacing and tunnel geometry, and should be confirmed by a project-specific lighting calculation.

06

Emergency tunnel lighting

Emergency lighting is a separate design exercise from normal tunnel working lighting. Because tunnelling is wholly dependent on artificial light, loss of the normal supply is a serious hazard: an appropriate emergency-lighting system must be provided to enable safe egress if the normal lighting supply fails. The arrangement is determined by the applicable standards, the tunnel risk assessment and the project requirements.

The emergency-lighting criteria below come from BS EN 1838:2024 and BS 5266-1:2025. They are emergency-lighting design criteria, not a percentage of normal tunnel lighting.

APPLICATION
ILLUMINANCE
REFERENCE CONDITIONS
Escape route lighting
1 lux minimum
At floor level across the full width of the escape route. For routes ≤2 m wide, exclude the outer quarter on each side; for routes >2 m, exclude the outer 0.5 m each side.
High-risk task area lighting
10% of normal maintained illuminance, or 15 lux — whichever is greater
On the reference plane for the task. Must reach full illumination within 0.5 seconds of supply failure. Relevant where a hazardous process must be made safe before evacuation.
Points of emphasis
5 lux vertical
At exit doors, refuge chambers, fire alarm call points, firefighting equipment and safety signs within the tunnel and at access points.
Open-area / anti-panic lighting
0.5 lux minimum
At floor level over the central core of the open area, excluding a 0.5 m border. Applicability depends on the geometry and use of the particular tunnel area — not every tunnel requires an open-area lighting calculation. Where a defined escape route passes through such an area, 1 lux applies along that route.

SOURCE: BS EN 1838:2024 \u00b7 BS 5266-1:2025

Emergency lighting is a separate design exercise from normal tunnel working lighting. An appropriate emergency-lighting system must be provided to enable safe egress if the normal lighting supply fails; the arrangement is determined by the applicable standards, the tunnel risk assessment and the project requirements. Required emergency duration depends on the evacuation strategy and whether reoccupation may occur before batteries are recharged.

07

Electrical design for long tunnel runs

Long tunnel lighting runs — particularly continuous LED strip installed along the full length of a tunnel — require electrical design consideration alongside the photometric design. The electrical design must address:

  • supply voltage and its suitability for the run length
  • run length and the cumulative load along the circuit
  • voltage drop over extended runs, which affects both output and safety
  • circuit loading and the number of feed points required
  • protective devices appropriate to the tunnel environment
  • cable and distribution arrangement, including routing and mechanical protection
  • emergency supply provision and its integration with the normal lighting circuits
  • redundancy where the risk assessment requires it, so that a single fault does not black out an extended section
  • environmental protection of electrical components against water, dust and mechanical damage in the tunnel

Cable sizes, breaker ratings and maximum circuit capacities cannot be prescribed generically; they must be determined for each project based on the actual run length, load, supply arrangement and environmental conditions.

08

Typical LMX Tunnel Lighting Design

Actual illuminance achieved in a tunnel depends on the tunnel dimensions, the LMX product and output selected, mounting position, spacing between run lengths, surface reflectance, environmental conditions and the maintenance factor applied. Because every tunnel is different, LMX does not publish generic “lux per metre” figures as if they were universal results.

A project-specific lighting design calculates the achieved illuminance, uniformity and glare for the actual tunnel layout and product configuration. LMX offers this as a service, based on:

  • tunnel width and height
  • required lighting level for each tunnel zone (walkways, working areas, tunnel face)
  • LED strip output and configuration
  • mounting position and height
  • surface characteristics and reflectance
  • location and extent of work areas
  • emergency lighting requirements

Verified project-specific calculations may show average lux, minimum lux, uniformity and the proposed layout, together with the emergency lighting arrangement.

Need a project-specific tunnel lighting calculation? Our engineering team can calculate achieved illuminance, uniformity and glare for your actual tunnel layout and product configuration.

REQUEST A LMX TUNNEL LIGHTING DESIGN
09

Relevant LMX products

10

Typical LMX Tunnel Lighting Examples

The examples below are illustrative approximate design examples only, not final project-specific photometric calculations.

01

4m Wide Tunnel — 1,200 lm/m LMX LED Strip

TUNNEL WIDTH
Approximately 4m
CONTINUOUS LED STRIP OUTPUT
1,200 lm/m
TYPICAL APPLICATION
Temporary tunnel access / construction lighting
DESIGN CONSIDERATION
30 lux walkway / access areas and higher lighting levels where active work is taking place
CONFIRMATION
Final mounting position, number of runs and achieved lux must be confirmed by project-specific lighting calculation
02

14m Wide Tunnel — 2,500 lm/m High-Output LMX LED Strip

TUNNEL WIDTH
Approximately 14m
HIGH-OUTPUT CONTINUOUS LED STRIP
2,500 lm/m
TYPICAL APPLICATION
Large tunnel excavation / major infrastructure works
LIGHTING ARRANGEMENT
Can be assessed as either single-side or two-side continuous lighting, depending on the required illuminance and uniformity
DESIGN CONSIDERATION
30 lux access / walkway areas and approximately 100 lux for general tunnel working areas, subject to the actual project requirements
CONFIRMATION
Final layout and achieved lux must be confirmed by project-specific lighting calculation

Illustrative examples only. Actual illuminance depends on tunnel geometry, mounting height and position, surface reflectance, obstructions and the selected lighting arrangement. LMX can provide a project-specific lighting calculation.

Need a tunnel lighting design? Our engineering team can prepare a project-specific tunnel lighting calculation for your actual tunnel geometry and product configuration.

REQUEST A TUNNEL LIGHTING DESIGN

Lighting requirements can vary according to the specific task, tunnel conditions, risk assessment and project specification. The applicable standards and project requirements should be confirmed for each installation.